| Error Code |
What It Means |
Common Causes |
Common On: |
| A6 |
Indoor fan motor problem |
Fan motor fault, loose wiring/connection, indoor circuit board issue |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Heat Reclaim Ventilator |
| C4 |
Sensor fault on the indoor heat exchanger (liquid pipe) |
Sensor failure, loose connection, indoor circuit board issue |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Heat Reclaim Ventilator
‣ Chiller
‣ Fan Coil |
| C5 |
Sensor fault on the indoor heat exchanger (gas pipe) |
Sensor failure, loose connection, indoor circuit board issue |
‣ Split/Multi-split
‣ VRV
‣ Packaged
‣ Heat Reclaim Ventilator
‣ Chiller |
| C9 |
Indoor air temperature sensor problem |
Sensor failure, loose connection, indoor PCB issue |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Heat Reclaim Ventilator
‣ Fan Coil |
| E3 |
High-pressure protection has activated |
Dirty outdoor coil, blocked airflow, refrigerant restriction, pressure switch fault |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| E4 |
Low-pressure protection has activated |
Low refrigerant, pressure sensor fault, outdoor PCB issue |
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| E5 |
Compressor or inverter is overheating, or a motor fault |
Compressor strain/lock, inverter PCB fault, wiring connection issue |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| E6 |
Compressor overcurrent or the compressor is locked |
Compressor fault, PCB fault, stop valve closed (installation issue) |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| E7 |
Outdoor fan motor system problem |
Fan motor fault, wiring/connector issue, obstruction stopping fan blades |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| E8 |
Inverter compressor overcurrent |
Compressor fault, capacitor issue, PCB/power transistor fault |
‣ Split/Multi-split
‣ Chiller |
| F3 |
Discharge pipe temperature fault |
Sensor failure, abnormal discharge temperature, outdoor PCB issue |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| L5 |
Inverter overcurrent (protection fault) |
Compressor wiring fault, mechanical lock, inverter PCB fault |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| U0 |
Refrigerant issue (often low refrigerant) |
Refrigerant leak/shortage, wrong piping, sensor/pressure fault |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller |
| U2 |
Power supply issue or brief power failure |
Voltage fluctuation, momentary outage, wiring fault |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller
‣ Fan Coil |
| U4 |
Communication issue between indoor and outdoor units |
Wiring fault, outdoor unit power off, incorrect addressing, PCB fault |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Heat Reclaim Ventilator
‣ Chiller
‣ Fan Coil |
| U5 |
Communication issue between indoor unit and remote controller |
Remote/controller wiring issue, signal noise, PCB fault |
‣ Split/Multi-split
‣ SkyAir
‣ VRV
‣ Packaged
‣ Chiller
‣ Fan Coil |